C.8 Device Type: Pulse Reading Meter (PRM)
Real-Time Device Data Stored in PLC (PRM)
Real-Time Data Register Location in
PLC Block
Range or Contents
Instantaneous kW 0-1 0...4294967295 kW
kW demand (30 minutes) 2-3 0...4294967295 kW
Peak kW (30 minutes) 4-5 0...4294967295 kW
kW Hours 6-7 0...4294967295 kWh
kW demand (5 minutes) 8-9 0...4294967295 kW
New Snapshot Since Last 10 0 = No, 1 = Yes
Minutes Between Snaps 11 5, 30 minutes
Max Number of Snaps 12 1...65535 (snaps x 12)
Number of Hours Ago 13 0...65535 hours
Snapshot Year 14 0...99 (Modulo 100)
Snapshot Month 15 1...12 Month
Snapshot Day 16 1...31 Day
Snapshot Hours 17 0...23 Hours
Snapshot Minutes 18 0...59 Minutes
Snapshot Seconds 19 0...59 Seconds
Snapshot (most recent) 20-21 0...4294967295 kW
Snapshot 22-23 0...4294967295 kW
Snapshot 24-25 0...4294967295 kW
Snapshot 26-27 0...4294967295 kW
Snapshot 28-29 0...4294967295 kW
Snapshot 30-31 0...4294967295 kW
Snapshot 32-33 0...4294967295 kW
Snapshot 34-35 0...4294967295 kW
Snapshot 36-37 0...4294967295 kW
Snapshot 38-39 0...4294967295 kW
Snapshot 40-41 0...4294967295 kW
Snapshot (least recent) 42-43 0...4294967295 kW
1/1000 kWh Per Pulse 44 0...65535 (0.000 kWh)
Reserved 45-49 For Future Expansion
Device Command Data Retrieved From PLC (Pulse Reading Meter)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Clear Kilowatt Hours Unused for Command 1
2 = Clear Peak kW Demand Unused for Command 2
3 = Set kW Hours Per Pulse 1/1000 kWh Per Pulse (in 0.001 kWh)