Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 63
Alarm Status 22 Bit Contents
15 Overvoltage Setpoint
14 Voltage Unbalance Setpoint
13 Undervoltage Setpoint
12 Current Unbalance Setpoint
11 Neutral Overcurrent
10 Ground Overcurrent
9 Overcurrent Setpoint
8 Aux. Relay Closed
7 New Data in Alarm Log
6 Not Used
5 Not Used
4 Processor Error
3 Energy Value Overflow
2 EEPROM Data Corrupted
1 Function Range Error
0 Calibration Error
Reserved 23
25 For Future Expansion
Device Command Data Retrieved From PLC (Static Trip III)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Reset Kilowatt Demand Unused for Command 1
2 = Reset Kilowatt Hours (Total and Reverse) Unused for Command 2
3 = Close Breaker Unused for Command 3
4 = Open Breaker Unused for Command 4
5 = Clear Targets and Trip Status Unused for Command 5
6 = Close Auxiliary Contact Unused for Command 6
7 = Open Auxiliary Contact Unused for Command 7
Real-Time Device Data Stored in PLC (Static Trip III) (Continued)
Real-Time Data Register Location in
PLC Block
Range or Contents