SIMATIC S7-400
Function modules
FM 458-1 DP application module
FM 458-1 DP basic module
6/91
Siemens ST 70 · 2013
6
Overview
Basic module for handling arithmetic, closed-loop control and
open-loop control tasks
PROFIBUS DP interface for connection of distributed I/O and
drives
Modular design with expansion modules for I/O and commu-
nication
Technical specifications
6DD1 607-0AA2
Supply voltage
5 V DC Yes
24 V DC
Yes
permissible range (ripple included),
lower limit (DC)
4.8 V
permissible range (ripple included),
upper limit (DC)
5.25 V
Input current
Current consumption, typ. 1.5 A
Current consumption, max. 3A
Encoder supply
Backup battery
• Battery operation Yes
- Backup current, max.
15 µA
Memory
Backup
• present Yes; SRAM
Time of day
Clock
• Hardware clock (real-time clock) Yes
• Resolution
500 ms
Digital inputs
Number/binary inputs 8; Connector X2
Input voltage
• Rated value, DC 24 V
• for signal "0"
-1 to +6 V
• for signal "1"
13.5 to 33 V
Input current
• for signal "0", max.
(permissible quiescent current)
0mA
• for signal "1", typ.
3 mA; at 24 V
Input delay
(for rated value of input voltage)
• for standard inputs
- at "0" to "1", max. s
Interfaces
PROFIBUS DP
• equidistance Yes; With connection to interrupt
tasks
• Direct data exchange
(slave-to-slave communication)
Yes
Interrupts/diagnostics/
status information
Alarms
•Alarms Yes
Galvanic isolation
Galvanic isolation digital inputs
• Galvanic isolation digital inputs No; only via optional interface
modules
Dimensions
Required slots 1
Weight
Weight, approx. 1 000 g
Kap_06_eng.book Seite 91 Donnerstag, 2. Mai 2013 4:16 16