SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
Isolation modules
6/156
Siemens ST 70 · 2013
■
Overview
• Supports mixed operation of fail-safe signal modules in
safety mode and S7-300 standard modules in an ET 200M
when Cat. 4 or SIL 3 has to be achieved.
• The isolation module is not required if the safety class or safety
category to be achieved is less than SIL 3 or Cat. 4, respec-
tively.
When Cat. 4/SIL 3 is required, the isolation module must be
implemented in the following situations:
■
Technical specifications
■
Ordering data
Order No.
Application Isolation module must be used
Central use after CPU 31xF-2 DP
or CPU 31xF-2 PN/DP
• Only fail-safe modules in the tier Yes, behind the CPU
• Standard and fail-safe modules in the
tier
Yes, after the last standard module
and before the first fail-safe module
Central use after CPU 31xF-2 DP or
CPU 31xF-2 PN/DP in an expansion
rack
• Only fail-safe modules in the tier Yes, after the IM 36x
• Standard and fail-safe modules in the
tier
Yes, after the last standard module
and before the first fail-safe module
Distributed behind the IM 153-2
with copper connection
• Only fail-safe modules in the station Yes, after the IM 153-2
• Standard and fail-safe modules in the
station
Yes, after the last standard module
and before the first fail-safe module
Distributed behind the IM 153-2
with fiber-optic connection
• Only fail-safe modules in the station No
• Standard and fail-safe modules in the
station
Yes, after the last standard module
and before the first fail-safe module
6ES7 195-7KF00-0XA0
Weight
Weight, approx. 10 g
Isolation module
6ES7 195-7KF00-0XA0
for simultaneous operation of
fail-safe and standard modules in
an ET 200M
Isolation bus module 6ES7 195-7HG00-0XA0
for accommodating the isolating
module in an ET 200M