SIMATIC S7-400
Analog modules
SM 431 analog input module
6/68
Siemens ST 70 · 2013
■
Technical specifications (continued)
6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0
Supply voltage
Load voltage L+
• Rated value (DC) 24 V; Only required
for supplying 2-wire transmitters
• Reverse polarity protection Yes
Input current
from load voltage L+ (without load),
max.
400 mA 400 mA 400 mA
from backplane bus 5 V DC, max.
700 mA 1 200 mA 650 mA
Power losses
Power loss, typ. 4.5 W 4.6 W 3.3 W
Analog inputs
Number of analog inputs 16 8 8
Number of analog inputs
for voltage/current measurement
16 8
Number of analog inputs for resistance
measurement
8 8
permissible input voltage for voltage
input (destruction limit), max.
18 V; 18 V continuous, 75 V for 1 ms
(mark to space ratio 1:20)
35 V; 35 V continuous, 75 V for max.
1 s (mark to space ratio 1:20)
35 V; 35 V continuous, 75 V for max.
1 s (mark to space ratio 1:20)
permissible input current for current
input (destruction limit), max.
40 mA 32 mA
Input ranges (rated values), voltages
• 1 to 5 V Yes Yes
• -1 V to +1 V Yes Yes
• -10 V to +10 V Yes Yes
• -100 mV to +100 mV Yes
• -2.5 V to +2.5 V Yes Yes
• -20 mV to +20 mV Yes
• -25 mV to +25 mV Yes
• -250 mV to +250 mV Yes Yes
• -5 V to +5 V Yes Yes
• -50 mV to +50 mV Yes Yes
• -500 mV to +500 mV Yes Yes
• -80 mV to +80 mV Yes Yes
Input ranges (rated values), currents
• 0 to 20 mA Yes Yes
• -10 to +10 mA Yes Yes
• -20 to +20 mA Yes Yes
• -3.2 to +3.2 mA Yes
• 4 to 20 mA Yes Yes
•-5 to +5 mA Yes Yes
Input ranges (rated values),
thermoelements
•Type B Yes Yes
•Type E Yes Yes
•Type J Yes Yes
•Type K Yes Yes
•Type L Yes Yes
•Type N Yes Yes
•Type R Yes Yes
•Type S Yes Yes
•Type T Yes Yes
•Type U Yes Yes
Kap_06_eng.book Seite 68 Donnerstag, 2. Mai 2013 4:16 16