© 2010 Schneider Electric. All rights reserved. Page 85
ION Setup User Guide Using the Setup Assistant
LED Pulsing Screen
Some meters are preconfigured for LED pulsing. From the Energy Pulsing screen
in the Inputs/Outputs folder (or the Pulsing outputs folder, depending on the meter),
you can adjust LED pulse rates by modifying the Kt (pulse rate) registers. The Kt
value entered defines how much energy is accumulated before a pulse is sent.
Select the desired parameter and click Edit to set LED pulsing values.
NOTE
To configure the LED ports for a different pulsing application, you must re-link the Source input to the
output register of a different instantaneous power quantity in one of the Arithmetic modules. This is an
Advanced Configuration procedure. See “Working in Advanced Configuration Mode” on page 65.
Energy Pulsing Screen
If you want to use one of the digital outputs on your meter for energy pulsing
applications (Wh, kVAh, kVARh), configure it from the Energy Pulsing screen in the
Inputs/Outputs folder (or the Pulsing outputs folder, depending on your meter).
NOTE
If the ovld register is “Pulsing Suspended”, the energy is accumulating faster than the digital output can
pulse with the existing settings (the Calibration Pulser is in Overload State). Refer to the ION Reference,
Calibration Pulser Module, Detailed Module Operation section for details on how to configure the
Calibration Pulser Module’s settings.