ION Setup User Guide Using the Setup Assistant
Depending on your ION meter model, there are several available reports. Select
the desired report and click Display to view. You can choose the directory in which
you would like to save the file (the location defaults to the “Reports” folder in your
ION Setup directory).
Available reports vary depending on meter type:
Load Profile/Revenue Log generates a report showing values for the
parameters defined in the “Load Profile/Revenue Log Screen” on page 88.
Choose all available logs or query the meter by time, records, hours or days.
Click Save As to save your data in .hhf (hand-held format for MV-90), or select
one of the other available format types.
Refer to “HHF tab” on page 36 for instructions on how to configure ION Setup to export HHF files.
EnergyDemand Log shows the meter’s energy/demand log configuration.
Choose all available logs or query the meter by time, records, hours, or days.
Click Save As and save your data in the format desired.
Event Log shows meter events, including cause, value, effect and date/time.
This data can be saved as a .csv or .txt file.
The Event Log obtains its time records from the local time of the PC on which ION Setup is running, not
the meter’s local time.
Meter Configuration uploads the meter’s parameters and the set values of
those parameters. This report can be saved as a .txt file.
Configuration Comparison performs a text-based comparison between a
saved meter configuration and the connected meter and reports the differences.
Click Display, and browse to the saved meter configuration .txt file. In the
Comparison results screen click Details to display a full report which highlights
the differences in red.