APPENDIX 7
These circuits are intended for 24 hour alarm monitoring only.
UL 1076 requires an HTSW-1 tamper switch as well as a PAL-1 printer. Only Models
HTRI-S/-D/-R may be used as security points. A COMMUNICATION FAILURE with an
HTRI device configured for SECURITY results in a SECURITY EVENT as well as a
communication trouble. When installing an HTRI device in the Zeus tool, be sure to
set the device usage to security; otherwise, the device usage defaults to fire alarm.
• When setting the device address using the DPU, select the normally closed
alarm causing input.
• Connect only one switch per HTRI input.
For proprietary burglary
application (UL 1076):
• Use an HTSW-1 tamper switch to monitor the main enclosure.
• Monitor each HTRI-S/-D/-R related to this application for 24 hours by using a
listed motion detector (to prevent tampering).
• Monitoring of security points is performed at the PMI. The PMI is suitable
for installation at either the protected premises or remotely as a receiving
unit.
SECURITY POINT INSTALLATION