Vue de la page 14
DESCRIPTION 1-11
CHAPTER 1 | FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
LVM Live Voice Module The LVM Live Voice Module provides firefighters with a
means of sending live voice messages to specified audio
zones. The LVM has a push-to-talk switch on the micro-
phone, as well as a retractable coiled cord. Both the push-to
talk switch and the microphone are supervised. The LVM has
a built-in speaker to preview active tones and messages.
PFT Series The PFT Series FireFighters Telephones include models PFT
and PFT-P. Both models have a jack at the end of the phone
that plugs into either an FJ-303(SS) or FJ-304(SS) plate.
Model PFT-P has a “push-to-talk” button.
TZC-8B Telephone Zone The
TZC-8B
Telephone Zone Card provides a way for emergency
Card response personnel located throughout a building to speak with one
another during emergency situations. The card is located in any FireFinder-
XLS enclosure and is connected to jacks or FireFighter’s Telephone Sta-
tions located throughout the building.
Portable phones (Models PFT and
PFT-P) that plug into these jacks or FireFighter’s Telphone Stations (Model
FTS) can communicate to the FMT Firemans Master Telephone located at
the main enclosure or to telephones connected to the system.
ZAC-40 Zone Amplifier The ZAC-40 is a CAN data bus card that contains two speaker zones
Card and one 40 Watt audio amplifier capable of operating at 25, 70 or 100
VRMS. The two speaker zones can be wired to operate as either a
single Class A zone, a single Class B zone, or as two Class B zones
independently protected to provide split zone or interleaved speaker
zones.
The ZAC-40 can also be used as a backup amplifier to serve as a
backup for other ZAC-40 amplifiers in a one to one backup or one to
many backup.
The ZAC-40 contains a local external audio input circuit (0 dB) and a dry
contact input to switch on the amplifier and activate the two zones as
configured in the Zeus programmimg tool. The ZAC-40 is capable of
amplifying any one of the 8 audio channels that transmit from the
DAC-NET (Digital Audio Card-NET) via the internal digital audio ASI bus
(Audio Serial Interface).
CAN
ZONE ACTIVE
ZONE TROUBLE
ZONE GNDFAULT
OVERLOAD
NORMAL
LOW
ZONE
CARD FAIL
ASI FAIL
CAN FAIL
RESET
POWER
ZAC-40
+
-
1
+
-
2
CAN
TRBL
TRBL
TRBL
TRBL
ZONE 2 ACTIVE
ZONE 6 ACTIVE
ZONE 1 ACTIVE
ZONE 5 ACTIVE
ZONE 4 ACTIVE
ZONE 8 ACTIVE
TRBL
TRBL
TRBL
TRBL
ZONE 3 ACTIVE
ZONE 7 ACTIVE
CARD FAIL
GND FAULT
CAN FAIL
RESET
POWER
TZC-8B
+
-
1
+
-
2