PROFIBUS Interface for ultra-wave
TM
, Sonologic II & Weigh II
- 5 -
The Red and Green LED lights on the DP‑Slave indicate the status of the Probus connection. The Red LED is
CR1 STS and the Green LED is CR2 SPC STAT.
Possible status indications: Table 2‑1:
GREEN RED Meaning
ON Flash Probus connection is active. Red LED ashes to indicate data ow.
ON OFF Connection active with DP‑Master, but DP‑Slave is not transferring data. Check for
Rev. P or higher on Sono II.
OFF OFF DP‑Slave is not powered or hardware failure.
OFF 1x Flash
DP‑Slave is waiting to autobaud. Missing or bad connection with DP‑Master. Check wiring.
OFF 2x Flash DP‑Slave is waiting to be addressed. Check DP‑Master in cong software and verify it
matches DP‑Slave address.
OFF 3x Flash DP‑Slave has bad parameter or has lost connection. Check the GSE le was properly
imported and used to congure the DP‑Slave.
OFF Other Flash DP‑Slave hardware had an error initializing.