Power supply modules
3.15 Power supply modules PS 405 10A (6ES7405-0KA02-0AA0) and PS 405 10A R (405-0KR02-0AA0)
S7-400 Automation System Module Data
88 Reference Manual, Edition 09/2009, A5E00850736-06
Specifications of the PS 405 10A and the PS 405 10A R
Dimensions, weight, and cable cross-sections
Dimensions W x H x D (mm)
Weight
Cable cross-section
50x290x217
1.2 kg
3 x 1.5 mm
2
(litz wire with wire end ferrule, use
component conductor or flexible sheath cable)
Cable diameter 3 to 9 mm
Input parameters
Input voltage
Nominal value
24 VDC / 48 V / 60 V
Permissible range
Static: 19.2 to 72 VDC
Dynamic: 18.5 to 75.5 VDC
Nominal input current 4,0 A / 2,0 A / 1,6 A
Starting current inrush Peak value 18 A
A half-value width 20 ms
Output parameters
Output voltages
Nominal values
5.1 / 24 VDC
Output currents
Nominal values
5 VDC: 10 A
24 VDC: 1.0 A
Electrical parameters
Protection class in accordance with IEC 60536 I, with protective conductor
Overvoltage category II
Pollution degree 2
Nominal voltage U
e
0 < U
e
≤ 50 V
150 < U
e
≤ 300 V
Test voltage
700 VDC (secondary <-> PE)
2300 VDC (primary <-> secondary/PE)
Buffering of power failures >20 ms at a repeat rate of 1 s, complies with the
NAMUR recommendation NE 21
Power consumption 95 W
Power loss 20 W
Backup current Max. 100 µA at power off
Backup batteries (optional) 2 x Lithium AA,
3.6 V/2.3 Ah
Protective separation to IEC 61131-2 Yes