Analog modules
5.17 Diagnostics functions of analog modules
S7-400 Automation System Module Data
244 Reference Manual, Edition 09/2009, A5E00850736-06
Causes of errors and remedies for analog input modules
Table 5- 44 Diagnostic messages of the analog input modules, causes of errors and remedies
Diagnostic message Possible cause of error Remedy
Module error Any, the module has detected an error. -
Internal error Module has detected an error within the
automation system.
-
External error Module has detected an error outside of
the automation system.
-
Channel error Indicates that only certain channels are
faulty
-
External auxiliary voltage
missing
Load voltage to supply the 2-wire
transducer is missing on terminals L+ and
M.
Connect supply L+
Front connector missing Jumper between connections 1 and 2 in
the front connector is missing.
Install jumper
No module parameters Module requires information whether it
should operate with default system
parameters or with your parameters.
Message present after power on, until the CPU
has completed the transfer of parameters;
configure the module as required.
Incorrect parameters A parameter or combination of parameters
is incorrect; impermissible measurement
range, for example.
Reassign parameters to the module
Channel information
available
Channel error; module can provide
additional channel information.
-
Measuring range module
incorrect/missing
One or more measuring range modules is
missing or incorrectly inserted
Insert the measuring range modules on the
module according to the parameter assignment
of the type of measurement and the
measurement range
STOP mode No parameters have been assigned to the
module and the first module cycle has not
been completed.
If a reboot of the CPU all the digitized analog
values are in the intermediate memory, this
message is reset
EPROM error
RAM error
ADC/DAC error
Module is defective Replace the module
Hardware interrupt lost The module cannot send an interrupt,
since the previous interrupt was not
acknowledged; possible configuration
error.
Change the interrupt handling in the CPU
(change priority for interrupt OB; shorten
interrupt program).
Check the measuring range module Configuration /
programming error
Illegal parameters transferred to module
Reassign parameters to the module
Short-circuit to M A short-circuit to the M potential has
occurred on the sensor supply of 2-wire
transducers.
Eliminate the short-circuit.
Resistance of transducer circuit too high Use a different type of transducer, or modify the
wiring, for example, using a larger conductor
cross-section.
Open circuit between module and sensor Connect the cable
Disable channel ("Measuring type" parameter)
Wire break
Channel not connected (open)
Wire the channel