Digital modules
4.11 Digital input module SM 421; DI 16 x UC 120/230 V (6ES7 421-1FH00-0AA0)
S7-400 Automation System Module Data
132 Reference Manual, Edition 09/2009, A5E00850736-06
Specifications of the SM 421; DI 16 x UC 120/230 V
Dimensions and weight
Dimensions W x H x D (mm) 25 x 290 x 210
Weight Approx. 650 g
Module-specific data
Number of inputs 16
Cable length
Unshielded
600 m
Shielded
1000 m
Voltages, currents, electrical potentials
Number of simultaneously controlled inputs 16 at 120 V
8 at 240 V
16 with fan subassembly
Electrical isolation
Between channels and the backplane bus
Yes
Between channels
In groups of
Yes
4
Permissible potential difference
between M
internal
and inputs
230 VAC
Between inputs of different groups
500 VAC
Insulation resistance 4000 VAC
Current consumption
From the backplane bus (5 V)
Max. 100 mA
Power loss of the module Typ. 3.5 W
Status, interrupts, diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions None
Sensor selection data
Input voltage
Nominal value
120/230 VUC
For "1" signal
79 to 264 V AC
80 to 264 V DC
For "0" signal
0 to 48 V UC
Frequency band
47 to 63 Hz
Input current
With "1" signal
2 to 5 mA
With "0" signal
0 to 1 mA