Analog modules
5.9 Connecting sensors to analog inputs
S7-400 Automation System Module Data
222 Reference Manual, Edition 09/2009, A5E00850736-06
Connecting non-isolated sensors
Depending on local conditions or interference, potential differences U
CM
(static or dynamic)
can occur between the locally distributed measuring points. If the permitted value for U
CM
is
exceeded, there must be equipotential bonding conductors between the measuring points.
1
2
3
M+
M-
U
ISO
M+
M-
M
ANA
U
CM
(1) Non-isolated sensors
(2) Chassis ground
(3) Equipotential bonding conductor
M +: Measuring line (positive)
M -: Measuring line (negative)
M
ANA
: Reference potential of the analog measuring circuit
U
ISO
: Potential difference between M
ANA
and chassis ground
Figure 5-6 Connecting non-isolated sensors to an isolated AI
NOTICE
Do not use non-isolated 2-wire transducers and non-isolated resistance-type sensors!