Connection
6-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
6.4 Connecting alarm and warning outputs
During operation, the SICLOCK TC100 automatically carries out a range of func-
tion tests. If an error occurs, the device generates corresponding messages on
the display. A distinction is made between alarms and warnings.
There is an alarm output and a warning output for external monitoring on terminal
X2.
Figure 6-6 Alarm output X2-7 and warning output X2-8
Example:
Set the alarm output if there is no external synchronization.
Use the Configuration Tool to set the parameter entry /Synchronisation/Exen-
ded/Monitoring/Monitor Synchronization Status (0.09.14) = "Alarm" to activate
monitoring / alarm output in case of error.
;
;
;
Table 6-3 Parameters affecting the alarm behavior
/Synchronization/Extended/Monitoring/Monitor Synchronization Status (0.09.14)
/Network Settings/Ethernet 1/Extended Settings Adapter 1/Monitor Link Status (0.05.09)
/NTP Client/Monitoring/Monitor Server (0.18.04)
/Environment/Extended/Temperature/Monitoring (0.24.01)
Note
The contacts are designed as wire-break-proof, normally closed contacts. If there
is an alarm or warning, the corresponding contact opens.