Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Technical data 19 Jun 2009
8 Technical data
RDG100, RDG100T,
RDG110
RDG140, RDG160
Operating voltage AC 230 V +10/-15% SELV AC 24 V ± 20%
Frequency 50/60 Hz 50/60 Hz
Power consumption Max. 18 VA Max. 2 VA
Fan control rating
Q1, Q2, Q3-N
Y50 – G0
AC 230 V, max. 5(4) A
AC 230 V, max. 5(4) A
(RDG140)
SELV DC 0…10 V,
max. ± 1mA (RDG160)
Control outputs
Y1, Y2, Y3, Y4-N
Y11-N / /Y21-N (N.O.)
Y10-G0 / Y20-G0
Resolution
Current
AC 230 V, max. 1 A
(RDG100, RDG100T)
AC 230 V, max. 5(3) A
(RDG110)
SELV DC 0…10 V
39 mV
Max.
± 1 mA
All types
Multifunctional inputs, digital input
X1-M/X2-M
Temperature sensor input
Type
Digital input
Operating action
Contact sensing
Insulation against mains
D1-GND
Operating action
Contact sensing
Insulation against mains
QAH11.1 (NTC)
Selectable (NO/NC)
DC 0…5 V, max. 5 mA
N/A, mains potential
Selectable (NO/NC)
SELV DC 6…15 V, 3…6 mA
3.75 kV, reinforced insulation
Function input
External temperature sensor, changeover sensor,
operating mode switchover contact, dewpoint
monitor contact, enable electrical heater contact,
fault contact
Selectable
Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2 K (0.5…6 K)
1 K (0.5…6 K)
Setpoint setting and setting range
Comfort mode (P08)
Energy Saving mode (P11-P12)
Protection (P65-P66)
21°C (5…40 °C)
15 °C/30 °C (OFF, 5…40 °C)
8 °C/OFF (OFF, 5…40 °C)
Multifunctional inputs X1 / X2, digital input D1
Input X1
Input X2
Input D1
Selectable
Ext. temperature sensor
(P38 = 1)
Changeover sensor (P40 = 2)
Operating mode switchover
(P42 = 3)
Power supply
Outputs
Inputs