Siemens RDG160KN Manuel de service Page 34

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 60
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 33
34 / 60
Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
C1
RV
ON
OFF
12 3
This application is available with RDG110 only.
The diagrams below show the control sequences for 2-position control.
Heating mode with manual selection
(P01 = 2)
Cooling mode with manual selection
(P01 = 2)
½ SDH
1
0
½ SDH
w
Y
3181D115
T[°C]
C1 (H)
0
w
Y
12
T[°C]
RV
1
Y
½ SDC
1
0
½ SDC
w
T[°C]
C1 (C)
3181D116
Y12
1
0
w
T[°C]
RV
Heating and cooling mode (P01=04)
T[°C] Room temperature
w Room temperature setpoint
Y11 Control command “Compressor” (H)
Y21 Control command “Compressor” (C)
Y12 Control command “Reversing valve”
(heating = ON )
SDH Switching differential “Heating” (P30)
SDC Switching differential “Cooling” (P31)
Y
½ SDC
1
0
½ SDC
w
T[°C]
C1 (C)
½ SDH
½ SDH
C1 (H)
½
x
dz
½ x
dz
Y12
1
0
w
T[°C]
RV
3181D118
X
dz
Dead zone (P33)
Hardware
ON/OFF control
Vue de la page 33