Siemens MC55 Manuel d'utilisateur Page 97

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 469
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 96
MC55 AT Command Set
4.7 AT+IPR
s
m
obil
e
MC55_ATC_V01.05 Page 97 of 469 2/10/04
Confidential / Released
chronized after restarting the GSM engine (see chapter 4.7.1).
Parameter Description
bitrate per second (bps)
0 Activate autobauding (see chapter 4.7.1). This is not supported on ASC1.
300
600
1200
2400
4800
9600
14400
19200
28800
38400
57600
115200
230400
Notes
The factory default is autobauding enabled (AT+IPR=0) on ASC0 and 57600bps on ASC1. It will not be
restored with
AT&F.
The current setting of
AT+IPR will be preserved when you download firmware (i.e. a firmware update does
not restore the factory setting) or in the event of power failure.
Generally,
AT+IPR should be used as a standalone command. If nethertheless combinations with other com-
mands on the same command line cannot be avoided, there are several constraints to be considered:
- Avoid combinations with other AT commands.
- Take into account, that a delay of 100ms is required between the response to the last command (e.g. OK)
and the next command on the same line.
- When you enter
AT+IPR=0, autobauding will be activated after the response to the last command is
received.
- When local echo is active (
ATE1) and you enter AT+IPR=x with other commands you may encounter the
following problem: if switching to the new bitrate takes effect while a response is being transmitted, the
last bytes may be sent with the new bitrate and thus, not properly transmitted. The following commands
will be correctly sent at the new bitrate.
In order to account for greater ammounts of data it is recommended to choose a minimum bitrate of 2400 bps.
If the ME is operated in Multiplex mode we suggest a minimum bitrate of 4800bps.
When you run the multiplex mode, the write command
AT+IPR=<rate> won't change the current bitrate but
the new bitrate will be stored and becomes active, when the module is restarted.
<rate>
(num)(&V)
Vue de la page 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 468 469

Commentaires sur ces manuels

Pas de commentaire