7ML19985CL02 SITRANS LR 300 – INSTRUCTION MANUAL Page 79
mmmmm
Parameters
If the SITRANS LR 300 displays a full level, or if the reading fluctuates between a high
level and a correct level, set this parameter to elevate the TVT in this region and to de-
sensitize the receiver from any ‘base noise’ caused by internal antenna reflections and/or
nozzle echoes.
Entry:
0 = Off (not used).
1 = Use Learned TVT. (See Learned TVT Curve, in Example: After False Echo
Suppression, above.)
2 = Learn.
Set Up:
1. Perform this function at low tank levels.
2. Determine distance from radar unit to liquid level.
3. Select P838 and set [distance to liquid level minus 0.5m].
4. Select P837.
5. Press 2 and then press ENTER . P 837 will revert to 1 (use Learned TVT)
automatically after a few seconds.
Notes:
Press PROGRAM to toggle between RUN and PROGRAM mode.
Press TOGGLE twice to open parameter fields.
Example After Auto False Echo Suppression
TVT curve
(Learned)
Liquid
level
False echo
SITRANS LR 300.book Page 79 Monday, June 10, 2002 7:18 PM