7ML19985CL02 SITRANS LR 300 – INSTRUCTION MANUAL Page 65
mmmmm
Parameters
P210 mA Setpoint Parameter
Used to set the process level that corresponds to the 4 mA value. 4 mA always defaults to
0, and P201 determines whether this is a level, space, or distance measurement.
P211 mA Setpoint Parameter
Used to set the process level that corresponds to the 20 mA value. 20 mA always defaults
to 100%, and P201 determines whether this is a level, space, or distance measurement.
P212 mA Output Minimum Limit
Values 2 to 22.00
P213 mA Output Maximum Limit
Values 2 to 22.00
P214 4 mA Output Trim
Used to calibrate the mA output for 4 mA. The device mA output is pre-calibrated;
however, this parameter can be used to trim remote displays or inputs.
Steps:
1. Set P201 to 0 (manual).
2. Set P911 to 4 mA.
3. Record remote reading in mA.
4. Enter this value in P214.
5. Set P201 to previous setting.
P215 20 mA Output Trim
Used to calibrate the output for 20 mA. The device mA output is pre-calibrated; however,
this parameter can be used to trim remote displays or inputs.
Steps:
1. Set P201 to 0 (manual).
2. Set P911 to 20 mA.
3. Record remote reading in mA. Attach calibrated meter.
4. Enter this value in P215.
5. Set P201 to previous setting.
Values
Range: 0 to 22.00. Display P911
Related Parameters
P215 20 mA Output Trim
Values
Range: 0 to 22.00. Display P911.
Related Parameters
P214 4 mA Output Trim