575 I/O Module Specification & Pinouts
E-9
SIMATIC 545/555/575 System Manual
E.4 Discrete Relay Output Module
The discrete relay output module (PPX:5754916) allows the controller to
drive AC and DC loads of various voltage and current ranges. The loads can
be sourcing or sinking. Table E-8 shows module specifications.
Table E-8 Discrete Relay Output Module Specifications
Feature Description
Optical isolation 1500 Vrms
Isolation between commons 1500 Vrms
Isolation between chassis ground and
user circuits
1500 Vrms
Outputs 16
Commons 4
Fuses
One 3 A, 250 V, normal-blow, 5 x 20 mm
fuse per output (16 fuses total).
Replace only with UL/CSA-listed fuse.
Output type Non-latching, unprotected
Type of contact Form A
Operating voltage range
4.5 to 36 VDC
20 to 265 VAC
Maximum off-state leakage current 0.0 mA
Minimum load current per point 10.0 mA
Maximum delay time through module
10 ms, on to off;
10 ms, off to on
Temporary overload
*
5.0 A for 1 ms
Repetition rate 6 Hz maximum
Coil voltage requirement
24 VDC ±5% (22.825.2 V)
+5 V current consumption 0.9 A maximum
±12 V current consumption None
V
batt
current consumption
(+5 V STDBY)
None
Life cycles (@ 1 Hz repetition rate)
Full rated current
@ 0.5 A
@ 0.1 A
100,000
300,000
1,000,000
Maximum total relay contact resistance:
at 0.5 A to 2 A load currents = 400 mOhms
at 10 mA to 0.5 A load currents, use the following equation:
max R (ohms) = ((4.5 V/load current) x 0.05) + 0.15
*
The relay output module may be damaged if more than one channel is
overloaded at the same time, or if the temporary overload specification is
exceeded.