Cabling and Wiring the System
6-16
SIMATIC 545/555/575 System Manual
Installing Series 505 Remote I/O Cables (continued)
Use the following procedure to prepare Series 505 trunk line cables.
1. Strip back 1.50 inches (38 mm) of the sleeving on both ends of the
cable. There are three wires when the sleeving is stripped back; two
wires have color-coded insulation jackets and one (the shield) is bare.
2. At both ends of the cable, remove 0.13 in. (3.3 mm) of each color-coded
insulation jacket (both ends) to expose the bare wires.
3. At both ends of the cable, install each of the three exposed wires onto
terminal lugs according to directions provided by the manufacturer.
The size of the terminal lug depends on the type of terminal block used.
Consult your vendor for the appropriate terminal lug size.
Preparing Trunk
Line Cables