Installing 575 System Hardware
All VMEbus masters (including the 575 CPUs) require access to the
VMEbus daisy-chain control signals, including the bus grant and interrupt
acknowledge signals:
IACKIN* BG1IN* BG2OUT*
IACKOUT* BG1OUT* BG3IN*
BG0IN* BG2IN* BG3OUT*
BG0OUT*
Refer to Table 4-7 for pinouts.
Place any board that does not provide the BGxOUT* signals to the right of
any board that requires these signals. All of the 575 boards (CPUs and I/O
modules) pass through the daisy-chain signals.
Third-party slaves may occupy any unused address. There are two ways to
assign addresses to third-party slaves:
Calculate used address spaces and hard-assign an address.
Design the software on a third-party master CPU to log in slave boards
and to assign their addresses: refer to the SIMATIC 575 Interboard
Communication Specification (PPX:5758103).
!
WARNING
Memory overlaps in board addresses can cause erratic system operation.
Erratic system operation can cause death or serious injury to personnel, and/or
damage to equipment.
To minimize the risk of erratic system operation, ensure that there are no
memory overlaps in board addresses.
Daisy-Chain
Signals
Assigning
Addresses to
Third-Party Slaves
Vue de la page 135
1 2 ... 131 132 133 134 135 136 137 138 139 140 141 ... 321 322

Commentaires sur ces manuels

Pas de commentaire

Puls CD5.243 manuels

Manuels d'utilisation et guides de l'utilisateur pour Accessoires pour les appareils électriques Puls CD5.243.
Nous fournissons des manuels en pdf 1 Puls CD5.243 à télécharger gratuitement par type de document : Manuel de l'utilisateur






Plus de produits et de manuels pour Accessoires pour les appareils électriques Puls

Modèles Type de document
Aucun