Data Hiway Connections
Description
This section provides instructions for connecting the ANG_EN to an
existing Data Hiway.
Figure 2-6: Data
Hiway Connector
Data Hiway Port 1 &
2 Connections
Pin 1-ADH-A+
Pin 2-ADH-A-
Pin 3- Ground
Pin 4-ADH-B+
Pin 5-ADH-B-
Pin 6- Ground
Pin 1
Data Hiway Cable
The Advance Data Hiway requires a low capacitance, twin axial, 150-
ohm cable. The cable can be purchased from Siemens. See the table
below for ordering the correct cable:
Dual Channel Installation Standard Oval Cable
Siemens P/N 1681000-003
(Belden P/N SSD1743)
Dual Channel Installation Used for larger radius bends
Siemens P/N 1686002-002
(Alpha P/N 516689)
Single Channel Installation Siemens P/N 1686002-001
(Belden 9182, Alpha P/N 9283,
Manhattan P/N 39240)
20 Installation 2000590-001