Configuration Options with the ET 200M
3-17
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Procedure for Parameterizing Clock Synchronism
1. Settings at the CPU:
Object Properties of the CPU > Clock-Synchronized Interrupts tab
Set CPU clock-synchronized interrupt.
Select the used DP master system.
Select the desired subprocess image.
Recommended delay time:
Accept the default setting.
Memory Interrupts Time Interrupts Cyclic Interrupts Diagnostics / Clock
General Startup Clock-Synchr. Interrupts Cycle / Clock Flag Remanence
OB 61:
Priority
DP Master
System No.
Subprocess Image(s)
(e.g.: 1.4)
Time Delay
1 1 ms
Default
3.000
25
25
Protection
Figure 3-7 Clock-synchronized interrupts dialog box