Wiring
5-16
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Wiring with the Jumper
To wire the power supply module and IM 153-x, proceed as follows (see
Figure 5-6).
!
Warning
Make sure the ET 200M is de-energized before doing any wiring!
1. Open the front doors of the PS 307 and IM 153-x.
2. Undo the strain-relief assembly on the PS 307.
3. Strip the insulation from the power cable (230V/120V), and connect it to the
PS 307.
4. Screw the strain-relief assembly tight.
5. Insert the jumper and screw tight.
6. Close the front doors.
ET0047
4x
Strain-relief assembly
Power
cable
230 V/120 V
Figure 5-6 Wiring the PS 307 power supply module and the IM 153-x with the jumper
Setting the Switch for the Mains Voltage
Check that the switch for selecting the mains voltage is set correctly to your mains
voltage. This switch is always factory-set to 230 V on the PS 307. To select
another mains voltage, do the following:
1. Prize the cover off with a screwdriver.
2. Set the selector to your mains voltage.
3. Replace the cover.