Commissioning ProTool/Pro Runtime
5-13
ProTool/Pro Runtime User’s Guide
Release 12/99
Operate simulator
The following instructions provide a detailed description of the procedures for
operating the simulator.
Table 5-1 Simulator operation, step-by-step
Step Procedure
1 Start the simulator directly from the running configuration software by
clicking on the icon depicted or via menu options
File
Test
Start
Simulator
.
2
When the project is simulated for the first time, the simulator is stated with a
new, empty simulation table. If a simulation table already exists for the project,
this is opened.
All the settings are saved in simulation table *.sim defined for the simulation
of tags and area pointers (refer to Figure 5-1).
Note
Use the two menu options
File
Open
and
File
Save
to open and save the
simulation tables in the simulator. This does not open and save the project to
be simulated. To do this, use the corresponding menu options in the
configuration software.
3
Now manipulate the project tags and area pointers in the simulation table.
To do this, use the
Tag
column to select all the tags and area pointers to be
modified (refer to Footnote 1 on Page 5-11) and observed during the
simulation.
Click on the following symbol in the last line for each tag to be inserted:
4 Use the
Format
column to select the data format in which the values should be
represented in the table, e.g. Text, Dec, Hex or Bin.
The formats available are dependent on the configured data type.
5 Use the
Write Cycle
column to specify the intervals (in seconds) at which the
value is to be written in the project. The smallest unit that can be entered is
0.1 seconds.