System Messages
A-12
ProTool/Pro Runtime Users Guide
Release 12/99
RemedyEffect/CauseNumber
200002 Coordination is not executed at present
because the address format of the area
pointer does not match the internal storage
format.
– (Internal error)
200003 Coordination can be executed again
because the last error status has been
eliminated (return to normal operation).
200004 It is possible that coordination is not
executed.
200005 No more data is read or written.
This can have various causes:
S The cable is defective.
S The PLC does not respond, is defective,
etc.
S The system is overloaded.
Check that the cable is connected and the
PLC is in order.
Reboot the system if the system message is
displayed continuously.
210000 Jobs are not processed because the
address configured in the PLC does not
exist/has not been set up.
Change the address or set up the address in
the PLC.
210001 Jobs are not processed because the
address configured in the PLC cannot be
written to/read from.
Change the address or set up the address in
the PLC in an area which can be written
to/read from.
210002 Jobs are not executed because the address
format of the area pointer does not match the
internal storage format.
– (Internal error)
210003 The job mailbox is processed again because
the last error status has been eliminated
(return to normal operation).
210004 It is possible that the job mailbox is not
processed.
210005 A PLC job was triggered by an impermissible
number.
Check the PLC program.
210006 A fault occurred while attempting to execute
the PLC job. The PLC job is, therefore, not
executed.
Observe the subsequent/previous system
message, if appropriate.
Check the parameter types in the PLC job.
Compile the configuration again.
220000
2)
See footnote See footnote
220001 The tag is not downloaded because the
associated channel/the unit does not support
downloading the data type bool/bit.
Change the configuration.
220002 The tag is not downloaded because the
associated channel/the unit does not support
downloading the data type byte.
Change the configuration.
220003 The associated driver could not be uploaded.
It is possible that the driver is not installed.
Install the driver by re-installing ProTool/Pro
RT.