SED2 Operation & Maintenance Manual

Page 2

SED2 Operation & Maintenance Manual 2 Siemens Building Technologies, Inc. Manual Notations Notation Symbol Meaning DANGER: Indicates that pers

Page 3 - Maintenance Manual

SED2 Operation and Maintenance Manual 92 Siemens Building Technologies, Inc Parameter Description Unit User Setting Min Default Max Access Level P1

Page 4

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 93 Parameter Description Unit User Setting Min Default Max Access Level P0

Page 5

SED2 Operation and Maintenance Manual 94 Siemens Building Technologies, Inc Parameter Description Unit User Setting Min Default Max Access Level P0

Page 6

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 95 Parameter Description Unit User Setting Min Default Max Access Level P1

Page 7

SED2 Operation and Maintenance Manual 96 Siemens Building Technologies, Inc Parameter Description Unit User Setting Min Default Max Access Level r0

Page 8

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 97 Parameter Description Unit User Setting Min Default Max Access Level P09

Page 9 - Manual Organization

SED2 Operation and Maintenance Manual 98 Siemens Building Technologies, Inc Parameter Description Unit User Setting Min Default Max Access Level P2

Page 10 - Reference Documents

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 99 Parameter List r0000 Drive display (defined in P0005) Min: - Def: -

Page 11 - General

SED2 Operation and Maintenance Manual 100 Siemens Building Technologies, Inc Instructions: 1. Step 1: Set P0003=3 (expert user) 2. Step 2: Go to P

Page 12

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 101 P0040 Reset energy consumption meter Min: 0 Def: 0 Max: 1 Level 2

Page 13 - Environmental Conditions

Chapter 2 – Safety Instructions Siemens Building Technologies, Inc. 3 Chapter 2 — Safety Instructions General The following general guidelines are pr

Page 14 - Frame Sizes and Power Ranges

SED2 Operation and Maintenance Manual 102 Siemens Building Technologies, Inc r0054 CO/BO: Act. control word 1 Min: - Def: - Max: - Level 3 Bit

Page 15 - Mounting

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 103 P0100 Europe/North America power settings [kW or hp] Min: 0 Def: 0

Page 16

SED2 Operation and Maintenance Manual 104 Siemens Building Technologies, Inc P0310 Rated motor frequency Min: 12.00 Def: 50.00 or 60.00 Max: 6

Page 17 - Frame Size B Frame Size C

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 105 P0506[10] Parameter List Min: 0 Def: 754 Max: 4000 Level 3 Index:

Page 18

SED2 Operation and Maintenance Manual 106 Siemens Building Technologies, Inc P0705[2] Function of digital input 5 Min: 0 Def: 15 Max: 99 Level

Page 19 - Motor Cable Length

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 107 r0747 CO/BO: State of digital outputs Min: - Def: - Max: - Level

Page 20

SED2 Operation and Maintenance Manual 108 Siemens Building Technologies, Inc P0757[2] Value x1 of ADC scaling [V/mA] Min: 50.0 Def: 0 Max: 150

Page 21 - Torx driver T20

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 109 P0779[2] Value x2 of DAC scaling Min: -99999.0 Def: 100.0 Max: 99

Page 22 - Power and Motor Connections

SED2 Operation and Maintenance Manual 110 Siemens Building Technologies, Inc r0948[12] Fault time Min: - Def: - Max: - Level 3 Data: Time stamp

Page 23 - :$51,1*

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 111 P0970 Factory reset Min: 0 Def: 0 Max: 1 Level 1 Enum: 0=Disabled

Page 24

SED2 Operation & Maintenance Manual 4 Siemens Building Technologies, Inc. Repair Only Siemens service departments, repair centers authorized by S

Page 25 - (Ground)

SED2 Operation and Maintenance Manual 112 Siemens Building Technologies, Inc P1001 Fixed frequency 1 Min: -650.0 Def: 0.00 Max: 650.00 Level 2

Page 26

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 113 P1025 Fixed frequency mode – Bit 4 Min: 1 Def: 1 Max: 3 Level 3 E

Page 27

SED2 Operation and Maintenance Manual 114 Siemens Building Technologies, Inc P1091 – P1094 Skip frequency 1 through 4 Min: 0.00 Def: 0.00 Max:

Page 28 - Control Terminal Connections

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 115 Min: 50 Def: 100 Max: 200 Level 3 Details: Defines search current u

Page 29 - 5 1 9 2 B 0 1 e n

SED2 Operation and Maintenance Manual 116 Siemens Building Technologies, Inc P1236 Compound braking current Min: 0 Def: 0 Max: 250 Level 2 Val

Page 30 - Chapter 5 — Commissioning

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 117 P1310 Continuous boost Min: 0.0 Def: 50.0 Max: 250.0 Level 2 Detai

Page 31 - DIP Switch Settings

SED2 Operation and Maintenance Manual 118 Siemens Building Technologies, Inc r1801 CO: Act. switching frequency Min: - Def: - Max: - Level 3 N

Page 32 - SED2 Operator Panels

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 119 P2010[2] USS baudrate Min: 4 Def: 6 Max: 12 Level 2 Enum: 4= 2400

Page 33 - Buttons on the BOP and AOP

SED2 Operation and Maintenance Manual 120 Siemens Building Technologies, Inc P2101[3] Stop reaction value Min: 0 Def: 0 Max: 4 Level 3 Details

Page 34

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 121 P2185, P2187, P2189 Upper torque threshold 1, 2, and 3 Min: 0.0 Def

Page 35 - Continued

Chapter 3 – Mechanical Installation Siemens Building Technologies, Inc. 5 Chapter 3 — Mechanical Installation Installation after Extended Storage Aft

Page 36 - Commissioning Prerequisites

SED2 Operation and Maintenance Manual 122 Siemens Building Technologies, Inc P2201 through P2215 Fixed PID setpoint 1 through 15 Min: -200.00 De

Page 37 - LR 39020

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 123 P2221[2]. P2222[2], P2223[2] BI: Fixed PID setp. select Bit 1, Bit 2,

Page 38

SED2 Operation and Maintenance Manual 124 Siemens Building Technologies, Inc P2240[2] Setpoint of PID-MOP Min: -200.00 Def: 10.00 Max: 200.00 L

Page 39

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 125 P2270 PID feedback function selector Min: 0 Def: 0 Max: 3 Level 3

Page 40

SED2 Operation and Maintenance Manual 126 Siemens Building Technologies, Inc r2294 CO: Act. PID output Min: - Def: - Max: - Level 2 Note: r229

Page 41 - SED2 Operation with the BOP

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 127 P2380[3] Motor hours run Min: 0 Def: 0 Max: 100000 Level 2 Index:

Page 42 - Testing with the AOP

SED2 Operation & Maintenance Manual 128 Siemens Building Technologies, Inc.

Page 43 - Chapter 6 — Programming

SED2 Operation & Maintenance Manual Addendum Siemens Building Technologies, Inc. 129 SED2 Operation & Maintenance Manual Addendum Table

Page 44

SED2 Operation & Maintenance Manual Addendum 130 Siemens Building Technologies, Inc. Chapter 1 - Mechanical Installation SED2 (IP20) Filters Dime

Page 45 - Instructions

Chapter 2 – Electrical Installation Siemens Building Technologies, Inc. 131 Chapter 2 - Electrical Installation EMC-Compatibility NOTE: The Siemens

Page 46 - SED2 Basic Functions

SED2 Operation & Maintenance Manual 6 Siemens Building Technologies, Inc. Height Above Sea Level: If installing the SED2 at an altitude of higher

Page 47 - DIN2 DIN1

SED2 Operation & Maintenance Manual Addendum 132 Siemens Building Technologies, Inc. • Check that the contactors in the control cabinet are supp

Page 48 - Digital Outputs

Chapter 2 – Electrical Installation Siemens Building Technologies, Inc. 133 5192J101L1L2L326345 1. Incoming mains cable 2. Control cable 3. Motor ca

Page 49 - Analog Inputs

SED2 Operation & Maintenance Manual Addendum 134 Siemens Building Technologies, Inc. Power Connection for Drives with a Built-in EMC Filter SED2

Page 50 - Time in ms

Chapter 2 – Electrical Installation Siemens Building Technologies, Inc. 135 SED2 drives (frame sizes D, E, and F) include a built-in, prewired, EMC f

Page 51 - Analog Outputs

SED2 Operation & Maintenance Manual Addendum 136 Siemens Building Technologies, Inc. L3L2L1PE PEL3L2L1UVWUWV5192Z12enEMC filter SED23-PhaseMotor

Page 52 - P0776, Type of analog output

Chapter 2 – Electrical Installation Siemens Building Technologies, Inc. 137 Operation with a Residual Current Device (RCD) If a residual current devi

Page 53 - Frequency Setpoint (P1000)

SED2 Operation & Maintenance Manual Addendum 138 Siemens Building Technologies, Inc. Chapter 3 - Programming Bypassing the SED2 There are applica

Page 54 - OFF Functions

Chapter 3 – Programming Siemens Building Technologies, Inc. 139 P1262, Bypass dead time Time delay between switching contactors (SED2 to bypass/cont

Page 55 - SED2 HVAC Functions

SED2 Operation & Maintenance Manual Addendum 140 Siemens Building Technologies, Inc. Hibernation Mode If the SED2 reaches the hibernation setpoin

Page 56 - CONTROLLER

Chapter 3 – Programming Siemens Building Technologies, Inc. 141 Setting range: 0 to 254 second P2392, Restart frequency Hibernation restart frequenc

Page 57 - 5192Z22en

Chapter 3 – Mechanical Installation Siemens Building Technologies, Inc. 7 Mounting Dimensions and Mounting for SED2 Drives (IP20) Table 1. Overall

Page 58

SED2 Operation & Maintenance Manual Addendum 142 Siemens Building Technologies, Inc. Chapter 4 - BiCo (Binector and Connector) Data Set Functions

Page 59 - 5192Z23de

Chapter 4 – BiCo Data Set Functions Siemens Building Technologies, Inc. 143 4. Run the SED2 using input 1 and operate the value using input 2. NOTE

Page 60 - Staging Pumps or Fans

SED2 Operation & Maintenance Manual Addendum 144 Siemens Building Technologies, Inc. Using Control and Status Words with BiCo Many SED2 read-only

Page 61 - Figure 35. Staging Pumps

Chapter 4 – BiCo Data Set Functions Siemens Building Technologies, Inc. 145

Page 62

SED2 Operation & Maintenance Manual 125-3202 Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 6008

Page 63

SED2 Operation & Maintenance Manual 8 Siemens Building Technologies, Inc. Dimensions and Mounting for SED2 Drives (NEMA Type 1) Table 2. Overal

Page 64 - P2378, Staging frequency

Chapter 3 – Mechanical Installation Siemens Building Technologies, Inc. 9 Dimensions and Mounting for SED2 Drives (IP54, NEMA Type 12) Table 3. Ove

Page 65 - Control (Commissioning)

SED2 Operation & Maintenance Manual 10 Siemens Building Technologies, Inc. Chapter 4 – Electrical Installation DANGER: • To ensure safe operat

Page 66

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 11 Motor Cable Length Maximum motor cable length is as follows: • 328 ft (10

Page 68

SED2 Operation & Maintenance Manual 12 Siemens Building Technologies, Inc. Operation in Ungrounded Systems IP20: SED2 drives (IP20) can operate i

Page 69 - Chapter 7 – Troubleshooting

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 13 1235192Z02 Figure 4. Disconnecting Y Capacitor in SED2 Frame Size B and C

Page 70

SED2 Operation & Maintenance Manual 14 Siemens Building Technologies, Inc. M6T30Torx screwdriver5192J17en Figure 6. Disconnecting Y Capacitor in

Page 71

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 15 :$51,1* • Verify that the SED2 and motor are correctly sized for the m

Page 72

SED2 Operation & Maintenance Manual 16 Siemens Building Technologies, Inc. 15192J12 Figure 8. Access to Connection Terminals for SED2 Frame Siz

Page 73

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 17 Power and Motor Terminal Layout (Ground)PE(Ground)L1L2L3DC+ DC-UVW5192Z05D

Page 74 - Warning Messages

SED2 Operation & Maintenance Manual 18 Siemens Building Technologies, Inc. Cable Cross-Sections for Power and Motor Cables Table 4. Cable Cross-

Page 75

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 19 Table 5. Cable Cross-Sections for input Voltage Range 3 AC 380V through 4

Page 76

SED2 Operation & Maintenance Manual 20 Siemens Building Technologies, Inc. Direction of Rotation To change the direction of rotation of the moto

Page 77

Chapter 4 – Electrical Installation Siemens Building Technologies, Inc. 21 L 1L 2L 3B - F i l t e rP EP EUVWP EP E2 0 0 - 2 4 0 V 3 A C3 8

Page 78 - Specification Options

SED2 Operation & Maintenance Manual 125-3202 Rev. 3, August, 2002

Page 79

SED2 Operation & Maintenance Manual 22 Siemens Building Technologies, Inc. Chapter 5 — Commissioning :$51,1* • Only authorized personnel tra

Page 80 - Unit-specific Data

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 23 DIP Switch Settings Motor Frequency & Units of Measurement Switches In all vers

Page 81

SED2 Operation & Maintenance Manual 24 Siemens Building Technologies, Inc. Prerequisites Prerequisites 9 Is the output of the SED2 motor rating?

Page 82

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 25 For information on setting and modifying parameters, see the Setting Parameters with

Page 83

SED2 Operation & Maintenance Manual 26 Siemens Building Technologies, Inc. Operator Panel/Button Function Description . Change to automatic cont

Page 84 - Options

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 27 Default Commissioning Settings Default settings for operation with the BOP are as fo

Page 85 - Using the Serial Interface

SED2 Operation & Maintenance Manual 28 Siemens Building Technologies, Inc. Parameter Description Default Value for North America (Europe) 0=Fa

Page 86 - Hardware Inputs and Outputs

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 29 Motor Data for Commissioning Parameters Motor parameters can only be modified if Com

Page 87 - Ordering Notes

SED2 Operation & Maintenance Manual 30 Siemens Building Technologies, Inc. Quick Commissioning Procedure P0010 Start Quick Commissioning0 = Read

Page 88 - Strategies for FLN (P1)

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 31 Setting Parameters with the BOP or AOP The following table describes the procedure f

Page 89

Rev. 3.0, September, 2002 NOTICE The information contained within this document is subject to change without notice and should not be construed as

Page 90 - Other Functionality

SED2 Operation & Maintenance Manual 32 Siemens Building Technologies, Inc. Step Action Resulting display 7 Press to return to P0010. 8 Press

Page 91

Chapter 5 – Commissioning Siemens Building Technologies, Inc. 33 NOTES: 1. The reset process takes approximately 10 seconds. 2. The parameter list

Page 92

SED2 Operation & Maintenance Manual 34 Siemens Building Technologies, Inc. Testing with the BOP 1. Restore the factory settings in the SED2. See

Page 93

Chapter 6 – Programming Siemens Building Technologies, Inc. 35 Chapter 6 — Programming Using the Parameters • Modify SED2 parameters using the BOP,

Page 94

SED2 Operation & Maintenance Manual 36 Siemens Building Technologies, Inc. SED2 Parameter Indices Certain parameters have indices. The indices pr

Page 95 - Chapter 9 – Communications

Chapter 6 – Programming Siemens Building Technologies, Inc. 37 L1L2L3B-FilterPEPEUVWPEPE200 - 240 V 3 AC380 - 480 V 3 AC500 - 600 V 3 ACAOUT1D / A20

Page 96 - N2 Bus Connections

SED2 Operation & Maintenance Manual 38 Siemens Building Technologies, Inc. SED2 Basic Functions Digital Inputs Stand-alone operation of the SED2

Page 97

Chapter 6 – Programming Siemens Building Technologies, Inc. 39 Factory settings: P0701 1 ON/OFF1 – Off as defined via Ramp-Down Time parameter P112

Page 98

SED2 Operation & Maintenance Manual 40 Siemens Building Technologies, Inc. 5192Z29DIN1 = 0DIN2 = 1DIN3 = 1DIN4 = 0DIN5 = 1DIN6 = 1AIN1 = 0AIN2 =

Page 99 - Inverter Unit (P0004=2)

Chapter 6 – Programming Siemens Building Technologies, Inc. 41 r0747, Invert digital outputs Shows the inverted state of the digital outputs as follo

Page 100 - Motor Data (P0004=3)

Table of Contents Siemens Building Technologies, Inc. i Table of Contents Chapter 1 — How To Use This Manual ...

Page 101 - Analogue I/O (P0004=8)

SED2 Operation & Maintenance Manual 42 Siemens Building Technologies, Inc. Index: P0756[0]: IN000=Analog input 1. P0756[1]: IN001=Analog input 2.

Page 102

Chapter 6 – Programming Siemens Building Technologies, Inc. 43 P0761, Width of deadband (V/mA) for analog inputs P0761 defines the deadband for the a

Page 103 - Motor Control (P0004=13)

SED2 Operation & Maintenance Manual 44 Siemens Building Technologies, Inc. 25 Present output voltage (scaled to P2001, Reference Voltage). 26 P

Page 104 - Communication (P0010=20)

Chapter 6 – Programming Siemens Building Technologies, Inc. 45 P0780: Defines y1 of the output characteristics (factory setting = 10). Example: The

Page 105 - PI Controller (P0004=22)

SED2 Operation & Maintenance Manual 46 Siemens Building Technologies, Inc. Start Motor Default setting: Terminal 5 (DIN 1, high). Additional sett

Page 106 - Factory settings (P0010=30)

Chapter 6 – Programming Siemens Building Technologies, Inc. 47 For starting the motor when OFF3 is set, the binary input must be closed (high). If OF

Page 107 - Parameter List

SED2 Operation & Maintenance Manual 48 Siemens Building Technologies, Inc. P2253P2261r 2262: setpoint source: setpoint filter timeconstant: filte

Page 108

Chapter 6 – Programming Siemens Building Technologies, Inc. 49 r2262 Check for setpoint (scaled PID setpoint in %). NOTE: SED2 must be set to automat

Page 109

SED2 Operation & Maintenance Manual 50 Siemens Building Technologies, Inc. Torque [Nm]Frequency [Hz]Threshold frequency 1 Threshold frequency 3Th

Page 110

Chapter 6 – Programming Siemens Building Technologies, Inc. 51 • Add ±15% to the torque derived from the setting of the frequency limit values to de

Page 111

SED2 Operation & Maintenance Manual ii Siemens Building Technologies, Inc. Buttons on the BOP and AOP...

Page 112

SED2 Operation & Maintenance Manual 52 Siemens Building Technologies, Inc. P0409, Pulses per Second at Rated Frequency Use parameter P0409 to set

Page 113

Chapter 6 – Programming Siemens Building Technologies, Inc. 53 MV M1 M2Pressure sensorto PID input ofvariable speed driveMotor starterVariablespeed d

Page 114

SED2 Operation & Maintenance Manual 54 Siemens Building Technologies, Inc. Motor MV, controlled by SED2Powert100%Total PowertMotor M1, switched b

Page 115

Chapter 6 – Programming Siemens Building Technologies, Inc. 55 Parameter Settings for Motor Staging (Commissioning) In general, the factory settings

Page 116

SED2 Operation & Maintenance Manual 56 Siemens Building Technologies, Inc. P2376, Delay override on motor staging/destaging The value of P2376 is

Page 117

Chapter 6 – Programming Siemens Building Technologies, Inc. 57 P0731, Function of Digital output 1, relay 1 (DOUT1) Parameter r2379 (relay 1 to motor

Page 118

SED2 Operation & Maintenance Manual 58 Siemens Building Technologies, Inc. Other Typical HVAC Applications The following table lists commonly def

Page 119

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 59 Chapter 7 — Troubleshooting Troubleshooting Using the Operator Panel If the motor

Page 120

SED2 Operation & Maintenance Manual 60 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Reaction F0002, Overvoltage • DC link v

Page 121

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 61 Error Cause Diagnosis/Remedy Reaction F0012, SED2 temperature signal lost • Wire

Page 122

Table of Contents Siemens Building Technologies, Inc. iii Dimensions and Weights...

Page 123

SED2 Operation & Maintenance Manual 62 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Reaction F0024, Rectifier overtemperatur

Page 124

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 63 Error Cause Diagnosis/Remedy Reaction F0041, Motor data identification failure •

Page 125

SED2 Operation & Maintenance Manual 64 Siemens Building Technologies, Inc. Error Cause Diagnosis/Remedy Reaction F0051, Parameter EEPROM fault •

Page 126

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 65 Error Cause Diagnosis/Remedy Reaction F0450, BIST tests failure Alarm value: 1.

Page 127

SED2 Operation & Maintenance Manual 66 Siemens Building Technologies, Inc. Reading Faults • OK FAULT (r0052, bit 3) is a read-only fault status

Page 128

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 67 Error Cause Diagnosis and Remedy Reaction A0504, SED2 overtemperature • The wa

Page 129

SED2 Operation & Maintenance Manual 68 Siemens Building Technologies, Inc. Error Cause Diagnosis and Remedy Reaction A0910, Vdc (max.) control

Page 130

Chapter 7 – Troubleshooting Siemens Building Technologies, Inc. 69 Error Cause Diagnosis and Remedy Reaction A0921, DAC parameters not set properl

Page 131

Chapter 8 – Technical Data and Options 70 Siemens Building Technologies, Inc. Chapter 8 — Technical Data Specification Options General Specifications

Page 132

Chapter 8 – Technical Data and Options Siemens Building Technologies, Inc. 71 Specification Description Digital inputs 6 (potential-free) inputs (ex

Page 133

SED2 Operation & Maintenance Manual iv Siemens Building Technologies, Inc.

Page 134

SED2 Operation & Maintenance Manual 72 Siemens Building Technologies, Inc. Dimensions and Weights Dimensions and weight (frame sizes A to C, IP20

Page 135

Chapter 8 – Technical Data and Options Siemens Building Technologies, Inc. 73 200V to 240V, ± 10%, 3 phase Output power (variable torque) IP code Ma

Page 136

SED2 Operation & Maintenance Manual 74 Siemens Building Technologies, Inc. 380V to 480V, ± 10%, 3 phase Output power (variable torque) IP code M

Page 137 - Manual Addendum

Chapter 8 – Technical Data and Options Siemens Building Technologies, Inc. 75 500V to 600V, ± 10%, 3 phase Output power (variable torque) IP code Ma

Page 138

SED2 Operation & Maintenance Manual 76 Siemens Building Technologies, Inc. Options Depending on the application, various options are available fo

Page 139 - EMC-Compatibility

Chapter 9 – Communications Siemens Building Technologies, Inc. 77 Chapter 9 — SED2 Communications Overview The SED2 drives are a family of inverters

Page 140 - 5192Z04en

SED2 Operation & Maintenance Manual 78 Siemens Building Technologies, Inc. RS-232 Personal computers use the RS-232 standard for interfacing to a

Page 141 - 5192J21us

Chapter 9 – Communications Siemens Building Technologies, Inc. 79 Point Database Table 8 provides point database information for Application 2722. Fo

Page 142 - Frame Sizes A through C

SED2 Operation & Maintenance Manual 80 Siemens Building Technologies, Inc. Verifying Parameters After the SED2 setup, verify the parameters by pe

Page 143 - Frame Sizes D through F

Chapter 9 – Communications Siemens Building Technologies, Inc. 81 Additional display points on the SED2 drive that may be of use: • INVERTER VER (Po

Page 144 - Connecting Multiple Motors

Chapter 1 – How to Use This Manual Siemens Building Technologies, Inc. 1 Chapter 1 — How To Use This Manual This manual is written for installers, te

Page 145

SED2 Operation & Maintenance Manual 82 Siemens Building Technologies, Inc. Slaving the Drive CAUTION: This strategy is not normally recommended

Page 146 - Chapter 3 - Programming

Chapter 9 – Communications Siemens Building Technologies, Inc. 83 Analog Inputs – Use ANALOG IN 1 (Point 45) and Analog IN 2 (Point 46) to monitor th

Page 147 - VSD contactor

SED2 Operation & Maintenance Manual 84 Siemens Building Technologies, Inc. Table 8. Point Database for Application 2722. Point Number Point Typ

Page 148 - Hibernation Mode

Chapter 9 – Communications Siemens Building Technologies, Inc. 85 Table 8. Point Database for Application 2722. Point Number Point Type Descriptor

Page 149 - P2392, Restart frequency

SED2 Operation & Maintenance Manual 86 Siemens Building Technologies, Inc. Table 9. Point Cross Reference to the SED2 Drive. Point Number Descr

Page 150 - How does BiCo work?

Chapter 9 – Communications Siemens Building Technologies, Inc. 87 Table 9. Point Cross Reference to the SED2 Drive. Point Number Descriptor Parame

Page 151

SED2 Operation & Maintenance Manual 88 Siemens Building Technologies, Inc. N2 Bus Connections The connections for the N2 network (Table 10) are l

Page 152

Chapter 9 – Communications Siemens Building Technologies, Inc. 89 Table 11. N2 Point Map. On Text Off Text Point Number Name Default Value Units

Page 153

SED2 Operation & Maintenance Manual 90 Siemens Building Technologies, Inc. Table 11. N2 Point Map. On Text Off Text Point Number Name Defaul

Page 154 - 125-3202

Appendix A: Parameter Reference List Siemens Building Technologies, Inc. 91 Appendix A: Parameter Reference List P0004 Parameter Filters/Categories