Item Names 41
Note All Alarms and Events are Read only (<EV_ID> is the ID defined by Step7, in
integer format, filled with leading zeros up to 6 characters; w=1 to 10; x=0 to 65,535;
n=0 to 65,534; m=0 to 65,532; y=0 to 7; v=1 to net PDU data size/type size - header
information, this size may vary). The longest string or array that can be read in a cyclic
service has the length of the PDU size minus 32 bytes. The longest string InTouch can
process is 131 bytes. Arrays are converted into HEXASCII strings representing the big
endian format of the binary data. The Wonderware Siemens SIMATIC NET S7 I/O
Server will not process writes (POKES) to Alarms and Events.
Note This version of Wonderware Siemens SIMATIC NET S7 I/O Server does not
allow acknowledgment of Alarms and Events.
Examples:
ALARM000010.TIME_STAMP
EVENT001234.ADD_VALUE2,LENGTH
ALARM000555.ADD_VALUE10,REAL0
EVENT000001.ADD_VALUE3,D0TOD
Some additional explanations:
EVENT_STATE: State of the Alarm/Event itself. If the Alarm/Event is
TRUE, then EVENT_STATE is TRUE and vice
versa. Please refer to the Step7 documentation for
more detailed information.
STATE: The state of the communication. Please refer to the
Step7 documentation for more detailed information.
ACK_STATE: The state of the acknowledgement of coming or going
Alarms/Events. Please refer to the Step7
documentation for more detailed information.
TIME_STAMP: Time stamp of the Alarm/Event, provided by the PLC.
NO_ADD_VALUES: Number of additional values that are sent with this
Alarm/Event message.
ADD_VALUEw,DATA_TYPE: Data type of a specific additional value of an
Alarm/Event
ADD_VALUEw,LENGTH: Length of a specific additional value of an
Alarm/Event
<EV_ID>: The event ID is created automatically by the Step7
programming software. In case of Alarms (FB33 to
FB36) this is the EV_ID-parameter of the function
block. The value of the parameter must be converted
from hexadecimal to decimal and then filled up with
leading 0to the length of 6 characters (e.g.: EV_ID:
DW#16#4E25 => <EV_ID>: 020005). In case of
Events (Generated by the symbol editor) this is the
„Message Number. This number is in decimal format
and must be filled with leading 0up to 6 characters
(e.g.: „Message number: 20000 => <EV_ID>:
020000).