Item Names 37
Counters
Data Format Item/Point Suffix Data Type Range
Word
Cx
None Integer 0...65535
Zx
None Integer 0 to 65535
BCD Integer 0 to 9999
KT Message 0.0 to 999.3
S5T Message 0ms to 2h46m30s
Note All Counters are Read/Write (x=0 to 65,535). The Wonderware Siemens
SIMATIC NET S7 I/O Server will process a write (POKE) to a Counter. Although the
S7 server allows to poke any word value into counters, the S7 PLC can only process
values in the range of 0..2457 or 0..999 (BCD).
Timers
Data Format Item/Point Suffix Data Type Range
Word
Tx
None Integer 0 to 14745
BCD Integer 0 to 9999
KT Message 0.0 to 999.3
S5T Message 0ms to 2h46m30s
TREALx
None Real 0.0 to 9990.00
Note All Timers are Read/Write (x=0 to 65,535). The Wonderware Siemens
SIMATIC NET S7 I/O Server will process a write (POKE) to a Timer. Although the
S7 server allows to poke any word value into timers, the S7 PLC can only process
values that represent a valid time format.
Block Items
Block items are available only if a BSEND routine is configured/programmed in the
remote PLC. With these items you are able to read huge data blocks (up to 64kByte)
out of the PLC. These items are only available if your SIMATIC NET driver supports
block services. For more information refer to your Siemens manuals.
Data Format Item/Point Suffix Data Type Range
Bit
BLd,Xx.y
Discrete 0 or 1
String
BLd,Sx,v
Message String
BLd,STRINGx,v
Message String
Byte
BLd,Bx
Integer 0 to 255
BLd,BYTEx
Integer 0 to 255
DT Message 1990-1-1-0:00:00.000 to
2089-12-31-23:59:59.999