4700 Power
Meter
The following table shows the points available for mapping in the Siemens
Model 4700 Power Meter:
Table 6: Siemens 4700 Power Meter
NPT
1
NPA
2
Unit Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Volt
Volt
Amps
Amps
KW
KVA
KVAR
KW
%
HZ
Volt
Amps
kWh
kWh-R
kQh
kW
MW
MVA
MVAR
MW
MWh
MWh-R
MQh
MW
L-N Average Phase Voltage
L-L Average Phase Voltage
Average Phase Current
Auxiliary Current Input
Total kW (power)
Total kVA
Total kVAR
kW Demand
Power Factor (positive values indicate lagging)
Frequency
Auxiliary Voltage Input
Ampere Demand
kW Hours
Reverse kW Hours
kVAR Hours
Maximum kW Demand
Total MW (power)
Total MVA
Total MVAR
MW Demand
MW Hours
Reverse MW Hours
MVAR Hours
Maximum MW Demand
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
Setpoint Alarm Condition Exists 0-nor, 1-ala
Relay 1 Status 0-rel, 1-oper
Relay 2 Status 0-rel, 1-oper
Relay 3 Status 0-rel, 1-oper
Status Input S1 0-gnd, 1-120V
Status Input S2 0-nor, 1-120V
Status Input S3 0-nor, 1-120V
Status Input S4 0-nor, 1-120V
Diagnostic Failure 0-nor, 1-ala
1 Network Point Type
2 Network Point Address
Continued on next page . . .
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine
the NPT (Network
Point Type) and
NPA (Network Point
Address). For
example, the
hardware reference
for the Frequency
point is AI10.
14 Metasys Integrator—Metasys Integrator Siemens Application