Metasys Integrator—Metasys Integrator Siemens Application 11
Metasys Integrator Unit Setup
To set up the Metasys Integrator unit, you use a portable PC connected to
Metasys Integrator Terminal Port. Metasys Integrator unit setup involves:
downloading the correct vendor communication table (.VCT file)
setting up the ports
assigning network addresses to the controllers
The following table provides setup information specific to Siemens
applications. For detailed procedures, see the Metasys Integrator unit
technical bulletins.
Table 3: Metasys Integrator Unit Setup for Siemens SEAbus
Applications
Vendor Communication Table (.VCT File)
Model 4300 Power Meter
SI_4300.VCT
Model 4700 Power Meter
SI_4700.VCT
Trip III/CPNX
SI_CPX.VCT
SAMMS Protective Relay
SI_SAMMS.VCT
Access I/O Addressable Relay
SI_ACCIO.VCT
Port Setup
Baud Rate
9600
Word Length
8
Stop Bit
1
Parity
None
Interface
RS-485
Network Setup
Vendor Address
0-254
Timeout Value
1000 ms
Poll Delay
Model 4300 Power Meter
Model 4700 Power Meter
Static Trip III/CPNX
SAMMS
Access I/O Addressable Relay
110 ms
110 ms
110 ms
110 ms
110 ms
Performance Guide
Approximate Scan Time for a Single
N2 Address
Model 4300 Power Meter
Model 4700 Power Meter
Static Trip III/CPNX
SAMMS
Access I/O Addressable Relay
1 second
2 seconds
2 seconds
1 second
1 second