Siemens P1 Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
Siemens APOGEE™ FLN (P1) Communication Kit
MN04008002E
For more information visit: www.EatonElectrical.com 5-1
February 2006
Chapter 5 — Siemens FLN (P1) Protocol
Overview
The P1 Protocol provides:
Direct control of Drive (e.g. Run, Stop, Direction, Speed reference, Fault reset)
Full access to necessary parameters
Monitoring of Drive status (e.g. Output frequency, Output current, Fault code)
P1 Point Map
Analog Input (AI) Point Map
Table 5-1: Analog Inputs (AI)
NPT Point Number Description Units
AI 3 FREQ OUTPUT Hz
AI 4 PCT OUTPUT %
AI 5 SPEED rpm
AI 6 CURRENT A
AI 7 TORQUE %
AI 8 POWER %
AI 9 DRIVE TEMP ° F (° C)
AI 10 DRIVE KWH kWh
AI 11 DRIVE MWH MWh
AI 12 RUN TIME Hours
AI 13 DC BUS VOLT V
AI 14 MOTOR VOLT V
AI 43 DRV ACT AO 1 mA
AI 45 DRV ACT AI 1 V
AI 46 DRV ACT AI 2 mA
AI 60 PID FEEDBACK %
AI 65 PID ERROR %
AI 70 DIN STATUS
AI 71 RO STATUS
AI 90 LAST FAULT
AI 91 PREV FAULT
Vue de la page 20