Siemens P1 Manuel d'utilisateur Page 20

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 19
Siemens APOGEE™ FLN (P1) Communication Kit
4-2 For more information visit: www.EatonElectrical.com
MN04008002E
February 2006
2. Set the FLN address for the device if desired (default address is 99).
Parameter P1.13.9 = (1 – 99)
The drive is set up for FLN network communication.
For more information about the description of some parameters, see the HVX9000 User
Manual, HVX9.11 or later version.
Communication Timeout
The RS-485 Communication Board initiates a communication error if communication is
broken for as long as defined by the Communication Timeout. Communication Timeout is
disabled when given a 0 value.
Communication Status
To see the present status of the communication board, enter the Communication status page
from the Monitor menu (G7.5.2). See Figure 4-1 and Table 4-2.
Figure 4-1: Communication Status
Table 4-2: Communication Message Indications
Messages Indications
Good messages
0 – 999 Number of messages received without communication errors
Error messages
0 – 64 Number of messages received with CRC or parity errors
Comm. status
Monitor
V1 V1
0.841
Good Message
Error Message
Vue de la page 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Commentaires sur ces manuels

Pas de commentaire