7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 201
mmmmm
Parameters
P843 Long Shot Frequency
Adjust the long shot transmit pulse frequency (in kHz).
This feature is automatically altered when Transducer (P004) is altered.
P844 Short Shot Width
Adjust the width (in ms) of the short shot transmit pulse.
This feature is automatically altered when Transducer (P004) is altered.
P845 Long Shot Width
Adjust the width (in ms) of the long shot transmit pulse.
This feature is automatically altered when Transducer (P004) is altered.
Primary Index Global
Values Range: 42kHz to 46kHz
Altered By P004 Transducer
Related
P841 Long Shot Number
P842 Short Shot
Frequency
P843 Long Shot Frequency
P845 Long Shot Width
Primary Index Global
Values Range: 0.000 to 5.000
Altered By P004 Transducer
Related
P840 Short Shot Number
P842 Short Shot
Frequency
P845 Long Shot Width
P850 Short Shot Bias
P851 Short Shot Floor
P852 Short Shot Range
Primary Index Global
Values Range: 0.000 to 5.000
Altered By P004 Transducer
Related
P841 Long Shot Number
P844 Short Shot Width
P843 Long Shot Frequency