7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 5
mmmmm
Specifications
Fixed
0.17% per °C deviation from programmed value
Outputs
Transducer drive
•315V peak
mA Analog
0-20 mA
4-20 mA
750 ohm maximum isolated
Resolution of 0.1%
Relays
1
•Six:
•4 control
2 alarm control
all relays rated 5A at 250Vac, non-inductive
Control Relays
4 Form A, NO relays (numbers 1,2,4,5)
Alarm Relays
2 Form C, NO, or NC relay (numbers 3,6)
Communication
RS-232 running Modbus RTU and ASCII via RJ-11 connector
RS-485 running Modbus RTU and ASCII via terminal blocks
Optional
SmartLinx
®
compatible
Inputs
mA (analog) (1)
0-20 or 4-20 mA, from alternate device, scalable
1.
All relays are certified only for use with equipment that fails in a state at or
under the rated maximums of the relays.