Alarm and fault messages
4.2 Alarm and fault messages
31
Table 4-3 Fault 0
(Alarm) General fault on transformer
Condition
The hardware contact in the power unit has tripped.
Causes
There is a defect in the inverter.
Measures
Replace the affected components.
Replace the drive.
Table 4-4 Faults 1 and 33
Message 1 (alarm): Inverter is signaling overtemperature, stage 1
Fault 33 (alarm): Inverter is signaling overtemperature, stage 2
Condition
An excessive heatsink temperature in the inverter has
been detected.
The thermoclick circuit for the reactors and transformers
has been interrupted.
Cooling system is not working properly
o Drive fan is not running
⇒ Fan motor is defective
⇒ Start capacitor is defective
⇒ No power supply to fan
⇒ USI is defective
⇒ Infeed transformer is defective
o Heatsink is blocked
o Drive fan speed is too low
⇒ Infeed transformer is connected to tap
460 V instead of 400 V
Heat generation is exceeding tolerance
o Current is too high
⇒ Parameter setting error (CU software –
current limit value)
o IGBT module defective
Fault in measured-value sensing
o Temperature sensor in heatsink is defective
o Temperature sensor connection is defective
o CU data input is defective
Causes
Reactor or transformer is overheating (fault 33 only,
without preceding warning level 1 in the PPsolar
event memory)
o Cooling system is not working properly
⇒ Housing fans are not running
⇒ Fans are defective
⇒ Thermostat is defective
⇒ Thermostat is incorrectly set
⇒ Air intake is restricted
⇒ Air inlet grille on housing is clogged
up
⇒ Air outlet is restricted