Alarm and fault messages
4.2 Alarm and fault messages
30
Table 4-2 ISO fault
ISO fault
Damaged, worn-through cables (loose, buffeted by
wind)
Cables damaged by animals
Water in junction box
Damaged insulation and ingress of water to cable
duct
Defective power unit
Bending device defective
Defect in PV module (damaged)
Causes
High air humidity (causes high leakage currents)
Diagnostics
Check the sensitivity (limit values) of the insulation
monitor using a decade resistor
Repair the cabling
Empty and dry out the junction boxes and / or cable
ducts
Measures
Repair / replace the drive