Modbus RTU Function Codes
24 Modbus® RTU Serial Communications User Manual 02/13
Device Class ID:
The Device Classification. (one byte) (byte 22)
Class ID Class
00 Generic Class (Fixed Address Mapable)
01-FF Future
Generic Class (00) Device Mapping:
Describes the I/O and feature mapping.
Number of
Records
Record
#1
Record
#2
Record
...
Record
#n
Number of records is always 5 for the Minitrend V5 and Multitrend Plus V5.
Number of Records:
1 Byte unsigned value 00-FFh (byte 23)
Record Description:
Byte Description
00 Type of Data Element
(See Data Element Values Table Below)
01 Starting Address of Data Element Record (High)
02 Starting Address of Data Element Record (Low)
03 Number of Data Elements (High)
04 Number of Data Elements (Low)
Data Element Values Table:
Value Description
00* Analog Inputs
01 Analog Outputs
02* Discrete Inputs
03* Discrete Outputs
04 Control Loops
05 Set Point Programmers
06* Math, Calculated Values, or Variables
07 Constants
08 Alarms
09* Totalizers
* These data elements are the 5 data records sent from the Minitrend and the
Multitrend Plus V5 recorders.