Modbus RTU Message Format
6 Modbus® RTU Serial Communications User Manual 02/13
Reserved Operands
Per the Standard certain exceptional forms of floating-point operands are excluded from the numbering
system. These are as follows:
EXCEPTION EXPONENT MANTISSA
+/- Infinity All 1’s All 0’s
Not-a-Number (NAN) All 1’s Other than 0’s
Denormalized Number All 0’s Other than 0’s
Zero All 0’s All 0’s
Modbus Double Register Format
Each IEEE 32-bit floating point number requires two consecutive registers (four bytes) starting with the
register defined as the starting register for the information. The stuffing order of the bytes into the two
registers differs among Modbus hosts. The selections are:
Selection Description Byte order
(See Figure
2-1)
Notes
FP B Floating Point Big Endian Format 4, 3, 2, 1
FP BB Floating Point Big Endian with
byte-swapped
3, 4, 1, 2
FP L Floating Point Little Endian Format 1, 2, 3, 4
FP LB Floating Point Little Endian with
byte-swapped
2, 1, 4, 3 Modicon and
Wonderware
standard
See IEEE Formats starting on next page.