Connection
5.4 Suitable cables for power supply and Ethernet
SCALANCE W770/W730
Operating Instructions, 11/2014, C79000-G8976-C325-04
29
The four-pin connecting socket has the following pin assignment:
Pin
Assignment
1
TX
2
RX
3
TX
4 RX
5.4
Suitable cables for power supply and Ethernet
Cable specification
The following table lists the requirements for a cable depending on the application.
Application
Specification
Direct 24 VDC supply
Round cable cross-section with
6 to 8 mm diameter.
Two-wire cable with 0.5 to 1.5 mm
2
cross-section
per wire.
Permitted tensile load at least
100 N.
UL listing: Type PLTC or ITC
Ethernet
1. IE FC TP standard cable GP 2 x 2 (type A)
Order no.: 6XV1 840-2AH10
2. IE TP torsion cable 2 x 2 (type C)
Order no.: 6XV1 870-2F
3. IE FC TP trailing cable 2 x 2 (type C)
Order no.: 6XV1 840 3AH10
UL listing: Type PLTC or ITC (the three named types
have this approval)