Siemens EH.75M.11. Spécifications Page 202

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 308
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 201
T400 Controller Facilities Manual
667/EB/20200/000 Page 19-9 Issue 9
Figure 19.4 - LMU Hold with losing phase delay
R/A
A
AMBER
AMBER
AMBER
AMBER
A
B
C
D
R/A
R/A
R/A
046 12
Time (secs)
E
F
G
H
STAGE 2......STAGE 1
Hold timer
started with
13 sec.
Intergreen
and gaining
phase delay
timers held.
Hold timer
expires and
hold
removed.
13 15 19
Intergreen
from C to H
started but
held.
The 6 sec
intergreen from C to
H only started when
the hold was
removed.
E & F would start
at this point but
are held off
Phase H would
start at this point
but is held off
Notes:-
(i) All intergreens are set to 6 seconds.
(ii) Hold time (SIE) set to 7 seconds.
(iii) 1st RLM fail active.
(iv) Losing phase delay of 6 seconds set from phase C.
(v) Phase C only conflicts with phase H.
Vue de la page 201
1 2 ... 197 198 199 200 201 202 203 204 205 206 207 ... 307 308

Commentaires sur ces manuels

Pas de commentaire