Siemens EF 847 Series Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 31
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
Page 30 of 31
Siemens Industry, Inc.
Data Link Layer Options
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________
MS/TP master (Clause 9), baud rate(s): 9600 bps, 19200 bps, 38400 bps, 76800 bps
MS/TP slave (Clause 9), baud rate(s): ____________
Point-To-Point, EIA 232 (Clause 10), baud rate(s): _________________
Point-To-Point, modem, (Clause 10), baud rate(s): _________________
LonTalk, (Clause 11), medium: _________________________________
Other: _____________________________________________________
Segmentation Capability
Able to transmit segmented messages Yes Window Size: 32
Able to receive segmented messages Yes Window Size: 32
Device Address Binding
Is Static Device Binding supported? Yes
Networking Options
Router, Clause 6
BACnet/IP (Annex J) to BACnet MS/TP
Annex H.3, BACnet Tunneling Router over UDP/IP
BACnet/IP Broadcast Management Device (BBMD)
Yes Does the BBMD support registrations by Foreign Devices?
Vue de la page 29