Siemens Industry, Inc.
Proven program sequences to match equipment
control applications.
Built-in energy management applications and
DDC programs for complete facility management.
Comprehensive alarm management, historical
data trend collection, operator control, and
monitoring functions.
Message control for terminals, printers, pagers,
and workstations.
Highly configurable I/O using Siemens state-of-
the-art TX-I/O™ Technology.
HMI RS-232 port, which provides laptop
connectivity for local operation and engineering.
Extended battery backup of Real Time Clock.
Persistent database backup and restore within the
controller.
Optional HOA (Hand/Off/Auto) module for
swappable and configurable HOA capability.
Optional extended temperature range for rooftop
installation.
Optional support for MS/TP devices.
Auto Save and persistent database backup and
restore within the controller.
PXM10T and PXM10S support: Optional LCD
Local user interface with HOA (Hand-off-auto)
capability and point commanding and monitoring
features.
BACnet Field Panel Web Server support: Web-
based Graphical User Interface (GUI) compatible
with BACnet® networks. Ideal for small or remote
facilities to monitor and control the Building
Automation System.
MS/TP Point Pickup Module (PPM) support:
Universal Inputs can be configured for analog or
digital input. Input/Output type is configured by
writing to BACnet object properties.
The Simple Network Management Protocol
(SNMP) Agent is a firmware feature that has been
added to BACnet firmware revision 3.2.3 and
later. The SNMP Agent allows points in the field
panel to communicate with an SNMP manager
over Ethernet.
The Compact Series
In addition to building and system management
functions, the Compact Series includes several styles
of controllers that flexibly meet application needs.
TC
The
-16
TC
Point count includes: 3 Universal Input (UI), 5
Universal I/O (U), 2 Digital Input (DI), 3 Analog Output
(AOV), and 3 Digital Output (DO).
-16 provides control of 16 points, including 8
software-configurable universal points.
TC
The
-24
TC
Point count includes: 3 Universal Input (UI), 9
Universal I/O (U), 4 Super Universal I/O (X), 3 Analog
Output (AOV), 5 Digital Output (DO).
-24 provides control of 24 points, including 16
software-configurable universal points.
TC
The
-36
TC
Point count includes: 18 Universal I/O (U), 6 Super
Universal I/O (X), 4 Digital Input (DI), and 8 Digital
Output (DO).
-36 provides control of 36 local points,
including 24 software-configurable universal points.
The TC-36 offers the flexibility of expanding the total
point count through a self-forming Island Bus. With
the addition of a TX-I/O Power Supply, up to two TX-
I/O modules can be supported. For more information,
see the
TX-I/O Product Range Technical Specification
Sheet
(149-476T
).