Configuration Examples
6-11
SIMATIC 505 PROFIBUS-FMS CP User Manual
Continue
configuring the FMS Read job by defining an FMS variable for the
FMS CP module at Station 2.
1.
Click on the FMS V
ariables icon of the configuration tree.
2.
Click on the New Item button on the toolbar
.
3.
Complete the fields listed below (and shown in Figure 6-9) to define the
FMS variable for Station 2:
Name: PumpControl
PLC Memory: V200
Data Type: UNSIGNED16
Variable Array: Yes
Array Elements: 10
Leave
the remaining fields at their default values.
✂
File Edit Transfer Options Diagnostics Help
Untitled
– COM5434
Reference
name of this variable
Edit
Module Local Configuration
FMS Connections
FDL Connections
Communication Jobs
FMS Jobs
Send-Receive Jobs
FMS Data T
ypes
FMS
FDL
FMS
P–P
S–R
DTs
Peerlink II Services
FMS V
ariables
Name:
File_AB
100
- PumpControl
PLC
Memory:
Access Rights:
Access Groups:
V200
RD=..a WR=..a
Click the New Item
button, or
, with FMS
V
ariables selected,
click the right
mouse button and
select New Item.
PumpControl
0,1,2,3,4,5,6,7
Password:
0
Data T
ype: UNSIGNED16
V
ariable Array:
Yes
Data T
ype Length (bytes):
2
Array Elements:
10
Index number is assigned
automatically by the software.
Info. Report Receiver?:
No
Connection: Pump
Use Index?:
No
0
Sub Index:
Figure 6-9 Defining
an FMS V
ariable
Defining an FMS
V
ariable for
Station 2
Commentaires sur ces manuels