Section 3 Configuration S800 I/O Configuration - Basic Rules and Examples
3BSE056248 35
Line/Master-redundant PROFIBUS Node with Redundant I/O
In total max 24 modules per CI840A (a redundant pair is 2 modules) but limited by:
PROFIBUS data capability.
CI840A/TB820 Power supply capability.
Required scan cycle time.
Modules not supported:
DI825, DO880, AI880A, DI830, DI831, DI880, DI885.
ABB Drives and SOE on DI840 are not supported.