Simatic/TI 505 Ethernet Driver Help
Device Setup
Supported Devices
CTI Interface Cards
CTI 2572, CTI 2572-A, and CP2572 Ethernet interface cards on TI series CPUs TI545, 555, and 565.
Simultaneous device connections are allowed. The model should be set to 505-CP2572. For more information,
refer to "Connection Limitations" below.
Siemens Interface Cards
505-CP1434-TCP Ethernet host card on TI Series CPUs TI545 and 565. Simultaneous device connections are
allowed. For more information, refer to the Siemens 505-CP1434-TCP User Guide.
CTI 2500 Controller Local Ethernet Port
The CTI 2500 controller's port supports up to three TCP connections (no UDP). Users can connect using the TCP
port 4450 or 1505. The model should be set to 505-CP2572.
Note: This affects all CTI 2500 controller models.
Supported Protocols
505: CAMP and CAMP Packed Task Code
IP: UDP and TCP / IP
Connection Timeout
This parameter specifies the time that the driver will wait for a connection to be made with a device. Depending
on network load, the connect time may vary with each connection attempt. The default setting is 3 seconds. The
valid range is 1 to 30 seconds.
Request Timeout
This parameter specifies the time that the driver will wait on a response from the device before giving up and
going on to the next request. Longer timeouts only affect performance if a device is not responding. The default
setting is 1000 milliseconds. The valid range is 100 to 30000 milliseconds.
Retry Attempts
This parameter specifies the number of times the driver will retry a message before giving up and going on to the
next message. The default setting is 3 retries. The valid range is 1 to 10.
Device IDs
Up to 2048 devices may be defined on a given channel. Each device on the channel must be uniquely identified
by its own IP address.
Connection Limitations
1. The default number of TCP connections allowed for the CTI 2572 / 2752-A and CP2572 cards is 8. When
configured from the PLC, this number may be set to a higher or lower number through the Start Network
Server command. In the CTI 2572 and CP2572 cards, this can be configured when started from PLC logic.
In the CTI 2572-A card, this can be configured when automatically started from EEPROM.
2. DIP Switch 3 in Switch Block 2 enables and disables the Data Share feature. When enabled, the number of
TCP server connections is automatically limited to two.
3. To connect to the PLC via the 505-CP1434-TCP card, configure a UDP Server Job in the card.
www. kepware.com