Simatic/TI 505 Ethernet Driver Help
L 11/12,
20/21
1=Auto-mode lock
M 12/13,
19/20
1=Cascade-mode lock
N 13/14,
18/19
1=Setpoint lock
O 14/15,
17/18
0=Output scale 0% offset
1=Output scale 20% offset - only valid if output is unipolar. Refer to Element T.
P 15/16,
16/17
P Q
0 1=No special function
1 0=Special function on the process variable
0 1=Special function on the setpoint
1 1=Special function on the output
Q 16/17,
15/16
R 17/18,
14/15
1=Freeze bias when output is out of range
S 18/19,
13/14
1=Ramp/Soak on the setpoint
T 19/20,
12/13
0=Output is unipolar
1=Output is bipolar
U 20/21,
11/12
0=PV is unipolar
1=PV is bipolar
V 21/22,
10/11
1=Perform derivative gain limiting
W 22/23, 9/10 Contains SF program number (if an SF program is scheduled to be called)
X 23/24, 8/9 Contains SF program number (if an SF program is scheduled to be called)
Y 24/25, 7/8 Contains SF program number (if an SF program is scheduled to be called)
Z 25/26, 6/7 Contains SF program number (if an SF program is scheduled to be called)
a 26/27, 5/6 Contains SF program number (if an SF program is scheduled to be called)
b 27/28, 4/5 Contains SF program number (if an SF program is scheduled to be called)
c 28/29, 3.4 Contains SF program number (if an SF program is scheduled to be called)
d 29/30, 2/3 Contains SF program number (if an SF program is scheduled to be called)
e 30/31, 1/2 Contains SF program number (if an SF program is scheduled to be called)
f 31/32, 0/1 Contains SF program number (if an SF program is scheduled to be called)
Note: If the bit is set to 1, the option is enabled.
LRSF Bit Definitions
Ramp / Soak Status Data Element Format
The server default settings are shown in bold.
MSB LSB
ABCD EFGH IJKL MNOP
The LRSF bit has the following format:
V/W, X/Y
V=0-based bit addressing. Bit 0 is MSB.
W=1-based bit addressing. Bit 1 is MSB (Simatic 505 documentation).
X=0-based bit addressing. Bit 0 is LSB.
Y=1-based bit addressing. Bit 1 is LSB.
Element LRSF
bit
Description
A 0/1,
15/16
1=Restart at the first step. To restart, toggle bit off, on, then off again. The restart
occurs on the trailing edge of a square wave.
B 1/2,
14/15
1=Hold at the current step. To hold, set bit on.
C 2/3,
13/14
1=Jog to next step. To jog, set bit on. Jog occurs on the rising edge of a square wave.
D 3/4, 1=Finish. Indicates ramp/soak is completed.
www. kepware.com
28