Configuring the PLC for Fisher PROVOX
D-5
TIWAY I Gateway User Manual
The
V
-memory block now has 9 data words (plus the status register) in each
PLC. From the 64-register limit, you would calculate that there could be a
maximum of 7 PLCs (64/9 = 7) configured like this and connected to a single
PCIU.
The following Relay Ladder Logic (RLL) programs for your Series 500/505 or
PM550 PLC will block and unblock data to be accessed by way of the
network.
BITP
A: STW1
N
= 10
BITP 1
A: STW1
N = 1
1
BITP 2
A: STW1
N = 12
BITP 3
A: STW1
N = 13
(cont’d)
C1
C1C1
C1
C1 C4
C1 C5
C1 C6
C3
I. Series 500 or Series 505 PLC Example Program
Relay
Ladder Logic
Program